logo

Technical Support

Set the Auto-scan Stop Channel

The RFC-1/B has an auto-scan command, 64. This command can be issued by a user to retrieve a complete set of channel readings using only one command. The reading always starts at channel 00. It ends with the user-adjustable stop channel.

The stop channel can be any channel from 01 through 63. The factory default setting is channel 07. The two digits of the channel number are programmed at addresses 1010 and 1011.

Instructions

These instructions will change the auto-scan stop channel from 07 to 15. This would be appropriate if a second RP-8 relay panel is added to a system.

Use the programming security code from your system when prompted at line 3.

  1. Connect to the RFC-1/B from either the local phone or a remote call.
  2. Once you have access to the system, enter programming mode: 80
  3. The RFC-1/B will prompt for the advanced programming security code: 4150
  4. The RFC-1/B will prompt for a four digit address: 1010
  5. The RFC-1/B will repeat the address and wait for a command.
  6. Enter the first digit of the new stop channel: 1
  7. Press the pound key to write the data at the address: #
  8. Enter the second digit of the new stop channel: 5
  9. Press the pound key to write the data at the address: #
  10. Exit the programming mode immediately by pressing the star key: *

It is important to press * and exit programming mode after the final value is entered.